Retractable supply posts
SE 80 Standard

Order No.:
MS SE 80-Sta-01
Delivery time
Technical data:
Protection class:
Protective equipment:
Nominal voltage/ Frequency:
Network:
Connected load:
max. permissible supply cable:
IP 44 for sockets
IP 55 for distributors
Protective conductor,
Protection class 1
230/400V, 50 Hz
TN-S system
approx. 130 kW
5 x 150 mm²
Equipment, Side A:
3 distributor, 10 modules
1 CEE 125A, 5-pol.
1 CEE 32A, 5-pol.
1 CEE 16A, 5-pol.
6 shock-proof sockets
1 RCD 125/0,3A, 4-pole
1 RCD 63/0,03A, 4-pole
1 mcb 125A, C, 3-pole
1 mcb 32A, B, 3-pole
1 mcb 16A, B, 3-pole
5 mcb 16A, B, 1-pole
1 D-02, 63A, 3-pole
Equipment, Side B:
3 distributors, 10 modules
1 CEE 63A, 5-pole
1 CEE 32A, 5-pole
2 CEE 16A, 5-pole
6 shock-proof socketes
1 RCD 63/0.3A, 4-pole
1 RCD 63/0.03A, 4-pole
1 mcb 63A, B, 3-pole
1 mcb 32A, B, 3-pole
2 mcb 16A, B, 3-pole
4 mcb 16A, B, 1-pole
1 mcb 2A, C, 1-pole (heating)
1 D-02, 63A, 3-pole
Weight:
Concrete pit + pit insert:
Equipped device column:
2120 kg
80 kg
Dimensions:
Hx Wx L:
Extendible height:
Paveable height of cover:
Loading capacity of cover:
Lifting mechanism:
Drainage connections:
1480 x 1400 x 1110 mm
590 mm
50 mm
C 250 as per DIN EN 124,
25t point load
Threaded spindle
2 x DN 40